ASCO JB8214235CCSA Solenoid Valve

Asco 8214 JB8214235CCSA Solenoid Valve, 3/4 in Nominal, NPT Connection, 2-Port/Way, 9.51 cu-m/hr, -20 to 125 deg F

Asco 8214 JB8214235CCSA Solenoid Valve, 3/4 in Nominal, NPT Connection, 2-Port/Way, 9.51 cu-m/hr, -20 to 125 deg F JB8214235CCSA

ASCO 214 Series gas shutoff valves are specifically designed for on-off control of fuel gas in commercial and industrial gas burners. Their unique double disc design with over travel provides redundant sealing for leak-tight shutoff on pilot or main gas lines. A double-solenoid gas train provides an exceptionally small footprint for space constrained applications. The valves are ideal for natural gas fired boilers, furnaces, grain dryers, kilns, gas generators and commercial kitchen and cooking equipment.
ASCO Solenoid Valve, Series: 8214, 3/4 in Nominal Size, NPT Connection, NC, 0 to 5 psi Pressure, 9.51 cu-m/hr Flow Rate, Media: Fuel Gas, 1-5/8 in Orifice, 2 Positions, 2 Ports/Ways, Aluminum Body, NBR Seal, NBR Disc, Stainless Steel Trim, -20 to 125 deg F

Body Material      :      Aluminum
Configuration      :      NC
Connection Type      :      NPT
Disc Material      :      NBR
Flow Rate      :      9.51 cu-m/hr
Media      :      Fuel Gas
Nominal Size      :      3/4 in
Number of Ports/Ways      :      2
Number of Positions      :      2
Orifice Size      :      1-5/8 in
Pressure Rating      :      0 to 5 psi
Seal Material      :      NBR
Series      :      8214
Temperature Rating      :      -20 to 125 deg F
Trim Material      :      Stainless Steel
  • Low pressure drop and extremely high flow capacity make the valve ideal in low gas supply pressure applications and locations
  • Visual indication of open and shut position meets NFPA and FM requirements for visual indication
  • Proof of closure switch meets agency and code requirements for an electrical interlock of valve closed position
  • 1/8 in NPT pipe taps with plugs provide easier routine testing
  • Broad ambient range of -40 to 140 deg F is ideally suited for frigid and hot environments
  • Zero differential piloted diaphragm
  • For on-off control of fuel gas in commercial and industrial gas burners
  • Wiring box with leads
  • pdfSpecification Sheet https://assets.unilogcorp.com/267/ITEM/DOC/Asco_8214G020_Specification_Sheet.pdf